YASKAWA FSDrive-MV1000 Parameter Manual page 86

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

1.4 Control Mode Dependent Parameter Default Values
u E3-01 (Motor 2 Control Mode) Dependent Parameters
Table 1.3 E3-01 (Motor 2 Control Mode) Dependent Parameters and Default Values
No.
C3-21
Motor 2 Slip Compensation Gain
C3-22
Motor 2 Slip Compensation Primary Delay Time
C4-07
Motor 2 Torque Compensation Gain
Motor 2 Torque Compensation Primary Delay
C4-08
Time
C5-21
Motor 2 ASR Proportional Gain 1
C5-22
Motor 2 ASR Integral Time 1
C5-23
Motor 2 ASR Proportional Gain 2
C5-24
Motor 2 ASR Integral Time 2
C5-26
Motor 2 ASR Primary Delay Time Constant
E3-04
Motor 2 Maximum Output Frequency
E3-05
Motor 2 Maximum Voltage
E3-06
Motor 2 Base Frequency
E3-07
Motor 2 Mid Output Frequency
E3-08
Motor 2 Mid Output Frequency Voltage
E3-09
Motor 2 Minimum Output Frequency
E3-10
Motor 2 Minimum Output Frequency Voltage
86
Name
Setting Range
Resolution
0.0 to 2.5
0.1
0 to 10000
1 ms
0.00 to 2.50
0.01
0 to 10000
1 ms
0.00 to 300.00
0.01
0.000 to 10.000
0.001 s
0.00 to 300.00
0.01
0.000 to 10.000
0.001 s
0.0 to 0.500
0.001 s
40.0 to 120.0
0.1 Hz
0 to 13000
1 V
0.0 to 120.0
0.1 Hz
0.0 to 120.0
0.1 Hz
0 to 13000
1 V
0.0 to 120.0
0.1 Hz
0 to 13000
1 V
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Control Modes (E3-01)
V/f (0)
OLV (2)
CLV (3)
0.0
1.0
3000
3000
1.00
1.00
200
50
5.00
5.000
5.00
5.000
0.004
60.0
60.0
60.0
2000
2000
2000
60.0
60.0
60.0
3.0
3.0
150
110
1.5
0.5
90
20
1.0
0.0
0
0.0
0

Advertisement

Table of Contents
loading

Table of Contents