F1-20, F1-36: PG Option Card Disconnect Detection
n
Sets whether the drive detects a fault or not when a PG-X3 card is disconnected.
No.
F1-20
PG Option Card Disconnection Detection 1
F1-36
PG Option Card Disconnection Detection 2
Setting 0: Disabled
Setting 1: Enabled
F1-30: PG Option Card Port for Motor 2 Selection
n
Specifies the drive port for the PG option card used for motor 2. Set this parameter when switching between motor 1 and
motor 2, where both motors supply a speed feedback signal to the drive. If the same PG card is being used for feedback
signals from both motors, then set F1-30 to 0. If each motor has its own PG card connected to the drive, then set F1-30 to
1.
No.
F1-30
Setting 0: CN5-C
Setting 1: CN5-B
u F2: Analog Input Card Settings
These parameters set the drive for operation with the analog input option card AI-A3. This section describes parameters
that govern operation with an input option card. Refer to the instruction manual packaged with the option card for
specific details on installation, wiring, input signal level selection, and parameter setup.
F2-01: Analog Input Option Card Operation Selection
n
Determines how the input terminals on the AI-A3 option card are used.
No.
F2-01
Setting 0: Separate functions for each terminal (V1, V2 replace analog inputs 1, 2)
Apply this setting to replace the drive analog input 1 and 2 by the option board terminals V1 and V2. Functions, gain, and
bias levels for an analog reference supplied by AI-A3 are set using the H3-
H3-04: Analog Input 1 Gain and Bias Settings on page
Note: Parameter setting error oPE05 will occur if option card terminals are set for separate input functions (F2-01 = 0) while b1-01 = 3.
Setting 1: Combine input terminal values to create frequency reference
This setting adds all three input signals on the AI-A3 option card are added together to create the frequency reference.
When the option card is the source of the frequency reference for the drive, parameter b1-01 must be set to 3. Gain and
bias settings for the frequency reference supplied from AI-A3 can be set using parameters F2-02 and F2-03.
F2-02, F2-03: Analog Input Option Card Gain, Bias
n
Parameter F2-02 sets the gain and parameter F2-03 sets the bias for the AI-A3 input signal when the card is used in the
combined input signals mode (F2-01 = 1). Both gain and bias are set as a percentage of the maximum output frequency.
No.
F2-02
F2-03
Note: Enabled only when F2-01 = 1.
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Parameter Name
Parameter Name
PG Option Card Port for Motor 2 Selection
Parameter Name
Analog Input Option Card Operation Selection
Parameter Name
Analog Input Option Card Gain
Analog Input Option Card Bias
Option Port
CN5-C
0, 1
CN5-B
0, 1
0, 1
0, 1
parameters as described in
193.
-999.9 to 999.9%
-999.9 to 999.9%
2.6 F: Option Settings
Setting Range
1
1
Setting Range
1
Setting Range
0
Setting Range
100.0%
0.0%
Default
Default
Default
H3-03,
Default
165

Advertisement

Table of Contents
loading

Table of Contents