YASKAWA FSDrive-MV1000 Parameter Manual page 73

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

No.
Name
(Addr.)
Frequency
o1-03
Reference Setting/
(502H)
Display Unit
V/f Pattern
o1-04
Frequency
(503H)
Parameter Setting
Unit
User-Set Display
o1-10
Units Maximum
(520H)
Value
User-set Display
o1-11
Units Decimal
(521H)
Display
o2-01
LO/RE Key
(505H)
Function Selection
o2-02
STOP Key Function
(506H)
Selection
o2-03
User Parameter
(507H)
Default Value
o2-04
Drive Model
(508H)
Selection
Frequency
o2-05
Reference Setting
(509H)
Method Selection
Operation Selection
o2-06
when Digital
(50AH)
Operator is
Disconnected
Motor Direction at
o2-07
Power Up when
(527H)
Using Operator
o2-09
Initialization Mode
(50DH)
Reference Voltage
o2-11
for Input Voltage
(50FH)
Detection
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
All Modes
Sets the units the drive should use to display the frequency reference and
motor speed monitors.
0: 0.01 Hz
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of motor poles setting in E2-04, E4-04,
or E5-04)
3: User-selected units (set by o1-10 and o1-11)
V/f
OLV
0: Hz
1: r/min
All Modes
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
o2: Digital Operator Keypad Functions
All Modes
0: Disabled
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.
All Modes
0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.
All Modes
0: No change.
1: Set defaults. Saves parameter settings as default values for a User
Initialization.
2: Clear all. Clears the default settings that have been saved for a User
Initialization.
All Modes
Enter the drive model. Setting required only if installing a new control
board.
All Modes
0: ENTER key must be pressed to enter a frequency reference.
1: ENTER key is not required. The frequency reference can be adjusted
using the up and down arrow keys only.
All Modes
0: The drive continues operating if the digital operator is disconnected.
1: A fault is triggered (oPr) and the motor coasts to stop.
All Modes
0: Forward
1: Reverse
This parameter requires that drive operation be assigned to the digital
operator.
All Modes
0: Japan
1: America
2: Europe
3: China
All Modes
Sets the primary rated voltage of the transformer.
Description
CLV
1.3 Parameter Table
Setting
common_
Default:
<10>
Min: 0
Max: 3
common_
Default:
<10>
Min: 0
Max: 1
Default:
<36>
Min: 1
common_
Max: 60000
Default:
<36>
Min: 0
Max: 3
Default: 1
common_
Min: 0
Max: 1
common_
Default: 1
Min: 0
Max: 1
common_
Default: 0
Min: 0
Max: 2
Default:
common_
Determined by
drive capacity
Min: –
Max: –
common_
Default: 0
Min: 0
Max: 1
Default: 0
common_
Min: 0
Max: 1
common_
Default: 0
Min: 0
Max: 1
common_
Default: 0
Min: 0
Max: 3
Default:
<6>
common_
Min: 0 V
Max: 20000 V
Page
232
233
233
233
233
234
234
234
234
235
235
235
73