YASKAWA FSDrive-MV1000 Parameter Manual page 53

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

H1-
Function
Setting
34
PID Soft Starter Cancel
35
PID Input Level Selection
Forward Run Command
40
(2-Wire Sequence)
Reverse Run Command
41
(2-Wire Sequence)
Run Command
42
(2-Wire Sequence 2)
FWD/REV Command
43
(2-Wire Sequence 2)
44
Add Offset Frequency 1
45
Add Offset Frequency 2
46
Add Offset Frequency 3
DC Injection Braking
60
Command
External Speed Search
61
Command 1
External Speed Search
62
Command 2
63
Field Weakening
67
Communications Test Mode
6A
Drive Enable
70
Drive Enable 2
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
H1 Contact Input Selections
All Modes
Open: PID soft starter is enabled.
Closed: Disables the PID soft starter b5-17.
All Modes
Closed: Inverts the PID input signal (1 to -1 or -1 to 1)
All Modes
Open: Stop
Closed: Forward run
Note: Cannot be set together with settings 42 or 43.
All Modes
Open: Stop
Closed: Reverse run
Note: Cannot be set together with settings 42 or 43.
All Modes
Open: Stop
Closed: Run
Note: Cannot be set together with settings 40 or 41.
All Modes
Open: Forward
Closed: Reverse
Note: Determines motor direction, but does not issue a Run command.
Cannot be set together with settings 40 or 41.
All Modes
Closed: Adds d7-01 to the frequency reference.
All Modes
Closed: Adds d7-02 to the frequency reference.
All Modes
Closed: Adds d7-03 to the frequency reference.
All Modes
Closed: Triggers DC Injection Braking.
V/f
OLV
Closed: Activates Current Detection Speed Search from the maximum output
frequency (E1-04).
V/f
OLV
Closed: Activates Current Detection Speed Search from the frequency reference.
V/f
OLV
Closed: The drive performs Field Weakening control as set for d6-01 and d6-02.
All Modes
Tests the RS-485 interface. Displays "PASS" if the communications test completes
successfully.
All Modes
Open: Drive disabled. If this input is opened during run, then the drive will stop as
specified by b1-03.
Closed: Ready for operation.
All Modes
Open: Drive disabled. If this input is opened during run, then the drive will stop as
specified by b1-03.
Closed: Ready for operation.
Description
common_
common_
common_
common_
common_
common_
common_
common_
common_
common
CLV
common
CLV
common
CLV
common
common_
common_
common_
1.3 Parameter Table
Reference
Page
178
178
178
178
178
178
178
178
178
178
179
179
179
179
179
179
53