u E: Motor Parameters
No.
Name
(Addr.)
E1-04
Maximum Output
(303H)
Frequency
E1-05
Maximum Voltage
(304H)
E1-06
Base Frequency
(305H)
E1-07
Middle Output
(306H)
Frequency
E1-08
Middle Output
(307H)
Frequency Voltage
E1-09
Minimum Output
(308H)
Frequency
E1-10
Minimum Output
(309H)
Frequency Voltage
E1-11
Middle Output
(30AH)
Frequency 2
<21>
E1-12
Middle Output
(30BH)
Frequency Voltage 2
<21>
E1-13
Base Voltage
(30CH)
E2-01
Motor Rated Current Sets the motor nameplate full load current in Amps. Automatically set
(30EH)
E2-02
Motor Rated Slip
(30FH)
E2-03
Motor No-Load
(310H)
Current
E2-04
Number of Motor
(311H)
Poles
E2-05
Motor Line-to-Line
(312H)
Resistance
E2-06
Motor Leakage
(313H)
Inductance
Motor Iron-Core
E2-07
Saturation
(314H)
Coefficient 1
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
E1: V/f Pattern for Motor 1
All Modes
To set linear V/f characteristics, set the same values for E1-07 and E1-09. In
this case, the setting for E1-08 will be disregarded. Ensure that the four
frequencies are set according to these rules:
E1-09 ≤ E1-07 ≤ E1-06 ≤ E1-11 ≤ E1-04
Note that if E1-11 = 0, then both E1-11 and E1-12 are disabled, and the
above conditions do not apply.
Output Voltage (V)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
Note: E1-07, E1-08 and E1-10 are available only in the following control
modes: V/f Control, Open Loop Vector.
E2: Motor 1 Parameters
All Modes
during Auto-Tuning.
All Modes
Sets the motor rated slip. Automatically set during Auto-Tuning.
All Modes
Sets the no-load current for the motor. Automatically set during
Auto-Tuning.
All Modes
Sets the number of motor poles. Automatically set during Auto-Tuning.
All Modes
Sets the phase-to-phase motor resistance. Automatically set during
Auto-Tuning.
All Modes
Sets the voltage drop due to motor leakage inductance as a percentage of
motor rated voltage.
V/f
OLV
Sets the motor iron saturation coefficient at 50% of magnetic flux.
Automatically set during Auto-Tuning.
Description
E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
CLV
1.3 Parameter Table
Setting
Default:
<10>
Min: 40.0 Hz
Max: 120.0 Hz
Default:
<10> <16>
Min: 0 V
Max: 13000 V
common_
Default:
<10> <16>
Min: 0.0 Hz
Max: 120.0 Hz
Default:
<10> <16>
Min: 0.0 Hz
Max: 120.0 Hz
Default:
<10> <16>
Min: 0 V
Max: 13000 V
Default:
<10> <16>
Min: 0.0 Hz
Max: 120.0 Hz
Default:
<10> <16>
Min: 0 V
Max: 13000 V
Default: 0.0 Hz
Min: 0.0 Hz
Max: 120.0 Hz
Default: 0 V
Min: 0 V
Max: 13000 V
Default: 0 V
Max: 0 V
Max: 13000 V
Default:
<6>
common_
Min: 10% of drive
rated current
Max: 200% of
drive rated current
Default:
<6>
common_
Min: 0.00 Hz
Max: 20.00 Hz
Default:
common_
<6>
Min: 0 A
Max: E2-01
Default: 4
common_
Min: 2
Max: 48
Default:
common_
<6>
Min: 0.000 Ω
Max: 65.000 Ω
common_
Default:
<6>
Min: 0.0%
Max: 40.0%
Default: 0.50
common
Min: 0.00
Max: 0.50
Page
156
156
156
156
156
156
156
156
156
<27>
156
157
157
157
157
158
158
158
39