Pdp Grounding - Alcatel-Lucent 1675 LambdaUnite Installation And System Turn-Up Manual

Multiservice switch, release 10.5.4
Hide thumbs Also See for 1675 LambdaUnite:
Table of Contents

Advertisement

System cabling and final assembly
...................................................................................................................................................................................................................................
Procedure 4-2: Ground wiring
Required grounding
Only the PDP must be grounded with the office ground as shown in the figure below. All
the other parts (rack, subracks, ...) are grounded as a result of the physical mounting
(physical/electrical connection of device and rack frame).
NOTE1: If isolated return wire is required (e.g. for the USA domestic
market), the U-bracket (connection between return and ground) has to be
removed!
NOTE2: To avoid hazard in case of reversed polarity at power connection, it
must be assured, that in the rack and subrack the DC-Return has no
connection to GND!
Figure 4-11 PDP grounding
Legend:
3
*
...................................................................................................................................................................................................................................
4-20
Grounding cable — CC848834974 (yellow/green)
The U-bracket has to be removed, if the return wire is grounded only
at the external battery (BDFB) source (e.g. valid for the USA
domestic market)
Alcatel-Lucent – Internal
Proprietary – Use pursuant to Company instruction
Power and ground cable installation
Procedure 4-2: Ground wiring
365-374-198R10.5.4
Issue 1 July 2009