Power, software, and circuit pack installation
...................................................................................................................................................................................................................................
3. Port units can be used in all universal slots.
However, port units with a transmission capacity of 20 Gbit/s (for example an
OP2G5D/PAR8 parent board, equipped with 8 optical modules) can only be used in
the universal slots 2, 4, 6, 8, 13, 15, 17, 19, 22, 24, 26, 28, 33, 35, 37, and 39. The slot
left to a slot where a 20-Gbit/s port unit is installed has to remain unequipped, i.e.
cannot be used for other applications. Please also refer to the diagram subsequent to
this list.
Cover all unequipped slots with blank front plates.
4. Lower-order cross-connection units:
If lower-order traffic (VT1.5, VC-12, or lower-order VC-3) is to be switched, a
lower-order cross-connection unit (LOXC) must be installed in dedicated universal
slots or slot combinations.
• Lower-order cross-connection units of type LOXC/1 (occupying 1 slot, with a
• Lower-order cross-connection units of type LOXC40G2S/1 (2 slots wide, with a
• Lower-order cross-connection units of type LOXC40G3S/1 (3 slots wide, with a
Please note that at most one LOXC equipment protection group may exist, i.e. at most
one worker slot can be used in combination with one protection slot (please also refer
to the 1675 LambdaUnite MSS User Provisioning Guide).
5. The Portless TransMUX unit (TMUX2G5/1), which occupies 1 slot, can be
provisioned in any universal slot of the system. However, please note that the
TMUX2G5/1 unit can only be used in combination with lower order cross-connection
units of type LOXC40G2S/1 and LOXC40G3S/1. Operation in combination with
LOXC/1 is not supported. This implies that the TMUX2G5/1 can only be used in Es
equipped with Controllers of type CTL/3T or CTL/3S. Es equipped with any other
type of Controller do not accept the provisioning of a TMUX2G5/1 unit.
...................................................................................................................................................................................................................................
5-48
switching capacity of 15 Gbit/s) can be used in the universal slots 4, 17, 18, 19,
37, and 39. The slots 4, 17, 18 and 37 are worker slots. The slots 19 and 39 are
protection slots. If the worker LOXC/1 is installed in slot 4, 17, or 18, then the
protection LOXC/1 must be installed in slot 19. If the worker LOXC/1 is installed
in slot 37, then the protection LOXC/1 must be installed in slot 39.
switching capacity of 40 Gbit/s) can be used in the universal slot pairs 3/4, 16/17,
18/19, 36/37, and 38/39. The slot pairs 3/4, 16/17 and 36/37 are worker slots. The
slot pairs 18/19 and 38/39 are protection slots. If the worker LOXC40G2S/1 is
installed in the slot pairs 3/4 or 16/17, then the protection LOXC40G2S/1 must be
installed in the slot pair 18/19. If the worker LOXC40G2S/1 is installed in the slot
pair 36/37, then the protection LOXC40G2S/1 must be installed in the slot
pair 38/39.
switching capacity of 40 Gbit/s) can be used in the universal slot 4 and 19 (worker
LOXC40G3S/1 in the slots 2/3/4, protection LOXC40G3S/1 in the slots 17/18/19)
Alcatel-Lucent – Internal
Proprietary – Use pursuant to Company instruction
Software and circuit pack installation
Configuration rules
365-374-198R10.5.4
Issue 1 July 2009