Procedure D-2: Mounting The 1663 Admu Subrack(S - Alcatel-Lucent 1675 LambdaUnite Installation And System Turn-Up Manual

Multiservice switch, release 10.5.4
Hide thumbs Also See for 1675 LambdaUnite:
Table of Contents

Advertisement

Mixed configuration: 1675 LambdaUnite MSS and 1663
ADMu
...................................................................................................................................................................................................................................

Procedure D-2: Mounting the 1663 ADMu subrack(s)

Before you begin
The procedure below describes the mounting of the 1663 ADMu subrack(s). A maximum
of two subracks can be mounted, one at the front and one at the back side of the rack.
Procedure
Proceed as follows to mount the 1663 ADMu subrack(s):
...................................................................................................................................................................................................
1
Mount one mounting bracket kit (CC848927224, item 1) on the subrack at mounting
position *3 as shown in the figure below.
...................................................................................................................................................................................................
Put the subrack on the bottom of the rack frame (rack front side) and fix it using M6 × 16
2
screws (CC901331421) with 7 ± 1.0 m [61.96 ± 2.65 lbs-in] torque. Use the hole
positions #47, #58, #65 and #77 (see
LambdaUnite MSS and 1663 ADMu)" (p.
OTE: The hole numbering is counted from top to bottom of the rack frame.
...................................................................................................................................................................................................
Repeat
3
mounted at the back side of the rack.
E
N D
O F
...................................................................................................................................................................................................
...................................................................................................................................................................................................................................
365-374-198R10.5.4
Issue 1 July 2009
Step 1
and
Step 2
in the case of a second 1663 ADMu subrack which has to be
S T E P S
Alcatel-Lucent – Internal
Proprietary – Use pursuant to Company instruction
Procedure D-2: Mounting the 1663 ADMu subrack(s)
Figure D-10, "Mounting positions (1675
D-15)).
D-5