Pdp Connection (Pi Cables) - Alcatel-Lucent 1675 LambdaUnite Installation And System Turn-Up Manual

Multiservice switch, release 10.5.4
Hide thumbs Also See for 1675 LambdaUnite:
Table of Contents

Advertisement

System cabling and final assembly
...................................................................................................................................................................................................................................
Figure 4-5 PDP connection (PI cables)
Ground (A+B)
Legend:
4, 5
+DC (rtn)
–DC
Ground
Routing
The PI cables should be routed as follows:
...................................................................................................................................................................................................
1
In the case of ...
side A
side B
...................................................................................................................................................................................................................................
365-374-198R10.5.4
Issue 1 July 2009
+DC (rtn)
(A+B)
PI cables (combined: yellow/green, red, blue)
red
blue
yellow/green
then ...
the PI cables, A-side (item 1), should be routed at the
right-rear side of the rack frame as shown in the figure
below.
the PI cables, B-side (item 2), should be routed at the
left-rear side of the rack frame as shown in the figure
below.
Alcatel-Lucent – Internal
Proprietary – Use pursuant to Company instruction
Procedure 4-1: Power wiring (PDP - PI/100)
-DC
(A+B)
Power and ground cable installation
PI cables, upper subrack
4A
4
5A
5
PI cables, lower subrack
4-11