Rubber Air Flow Baffles - Alcatel-Lucent 1675 LambdaUnite Installation And System Turn-Up Manual

Multiservice switch, release 10.5.4
Hide thumbs Also See for 1675 LambdaUnite:
Table of Contents

Advertisement

Power, software, and circuit pack installation
...................................................................................................................................................................................................................................
...................................................................................................................................................................................................
Check the following:
2
• All four fans are running.
• The air flow direction is from bottom to top. Use the "rubber air flow baffles" to
confirm the correct direction of air flow.
Figure 5-4 Rubber air flow baffles
...................................................................................................................................................................................................
To check the correct working of the "FAULT" LED remove both "POWER I PUT"
3
cables (A and B) from the fan unit. You can do this without switching off the power
supply.
Result:
...................................................................................................................................................................................................
Block one fan from moving with an obstacle (e.g. with a pen).
4
...................................................................................................................................................................................................................................
365-374-198R10.5.4
Issue 1 July 2009
The "PWR O " LED should be extinguished.
Alcatel-Lucent – Internal
Proprietary – Use pursuant to Company instruction
Powering
Procedure 5-2: Fan unit test