Alcatel-Lucent 1675 LambdaUnite Installation And System Turn-Up Manual page 430

Multiservice switch, release 10.5.4
Hide thumbs Also See for 1675 LambdaUnite:
Table of Contents

Advertisement

Stand-alone test procedures
...................................................................................................................................................................................................................................
Result:
• A switch to the standby CTL unit is caused without affecting traffic.
• The communication between WaveStar
• After about two minutes the standby CTL unit must be up and running.
The LED behavior on the standby CTL unit is as follows:
1. The "Active" LED flashes and the "Fault" LED is illuminated.
2. The "Active" LED flashes.
3. The "Active" LED flashes and the "Fault" LED is illuminated.
4. The "Active" LED flashes.
5. The "Active" LED is permanently illuminated.
Troubleshooting: If the conditions described above cannot be observed, refer to
appendix A, section
...................................................................................................................................................................................................
Re-insert the "CTL unit (active)".
2
Result:
1. The "Fault" LED is illuminated.
2. The "Active" LED flashes.
3. The "Active" LED and the "Fault" LED are extinguished.
After about four minutes the following must be observed:
• The "Active" LED on the standby CTL unit is permanently illuminated.
• The "Active" LED and the "Fault" LED on the "CTL unit (active)" are
Troubleshooting: If the conditions described above cannot be observed, refer to
appendix A, section
...................................................................................................................................................................................................
Perform an E login as described in chapter 7, section
3
(p.
7-7).
...................................................................................................................................................................................................
In the WaveStar
4
Result:
...................................................................................................................................................................................................
Select 1+1 Equipment ectlgrp in the Ptn Grp tab on the left-hand side of the window
5
and click the Select button.
...................................................................................................................................................................................................................................
8-44
The following can be observed:
This is the case when the standby CTL unit is marked with "(A)" in the CIT
System View and when its "Active" LED is permanently illuminated.
Procedure A-5: "CTL protection test failure" (p.
The LED behavior on the re-inserted CTL unit is as follows:
extinguished.
Procedure A-5: "CTL protection test failure" (p.
®
CIT System View, select Fault → Protection Switch....
The Switch Protection window appears.
Alcatel-Lucent – Internal
Proprietary – Use pursuant to Company instruction
Procedure 8-8: XC and CTL protection test
®
CIT and the E will be lost.
Procedure 7-1: " E login via OSI"
A-10).
A-10).
365-374-198R10.5.4