Place the RUN/SETUP jumper on the GALX-1134AN COP Interface Board to the RUN position.
Place the CN18 jumper on the GALX-1121An MAIN I/O board to No Test Mode 1 – 2.
Check that all the floor positions have been learned by selecting "Hoistway Tables"->" Dpy APS
Sel Valid Floors". The display should show a bit set for each valid floor.
Even though the car may start at floor 2 or 3 and even skip floors, the selector always starts
from one and increments the floors consecutively to show only valid floors. If there are 5 valid
floors, 5 bits must be set.
If a bit is zero, then run the car on inspection to that floor, make sure the car is dead level and
learn the floor from the procedure in sections 2.7.2.1 through 2.7.2.4., or from the LCD
Interface, "Elevator Setup"->" Learn Hoistway". Follow the prompt from the LCD display and
make sure not to mistakenly clear the hoistway table if floors have already been learned.
Select to NO when prompted to "Clear HW Table<U/D>? No".

3.3.4 Verify the Hoistway

With all the floors learned, run the car on inspection from bottom to top and verify that door zone signals
(UL, DL and DZ) and the NTS limit output modules (UN, DN, UT and DT) all work as expected.
The NTS top and bottom limits are set automatically from a table when the top or bottom floor
is learned respectively.
To manually change the NTS limits, perform the following items.
Change the "UT Limit Dist" or "DT Limit Dist" value from the "Adjustable Variables"->" NTS Proc
Adj Vars"->" menu. The value is set in inches from the terminal floor.
Run the car to the top or bottom floor, learn the floor and then run to the opposite floor and
again learn the floor. The new distances will be used at each terminal landing.
The selector will use the internal table value if limit distance parameter that is set to zero.
3.4

Adjust the Elevator

3.4.1 Automatic Run

Turn the "AUTO DOOR" switch to the "OFF" position and the "IND" switch to the "IND" position.
Take the car off of inspection operation to allow it to relevel to a floor. If the learn procedure
was successful, the elevator should be ready to make an automatic run.
From the Main CPU LCD interface, press the MODE button until the Elevator Status display is
shown. See Figure 3-4.
Pressing ENTER from any screen in the Elevator Status display will access the car call popup
window.