GALaxy eHydro Elevator Controller
Section 8 - Appendix A
Every safety precaution, whether or not specifically stated in this document, must be
implemented when installing, adjusting, or servicing elevator equipment. All safety
precautions must be followed to ensure the safety of elevator personnel and the general
public.
The test procedures outlined in this Appendix provide a guide for elevator personnel to
perform the specific tests in this Appendix. These test procedures are not intended to
override or circumvent any procedure or test that is mandated by the applicable codes and
the Authority Having Jurisdiction.
All temporary connections must be removed before placing the elevator in service.
If there are any questions in regard to the procedures for performing these tests with a
GALaxy eHydro controller, please call GAL Manufacturing toll free at 1-(877) 425-7778 for
free technical assistance.
8.1 Testing Stall Mode & Low Oil Operation
Turn the power of on the controller.
Temporarily remove SU-S12 and SUC-S11 connections from the controller.
Restore power to the controller.
If Return To Lobby is set to cycle doors at the lobby, set
The "RTL Dwell Tim" to control how long the doors will dwell before closing in return to lobby mode.
Temporarily set the "Stall Time" to 20.
Place a call in the UP direction.
The car will start going up, but when it changes to approach speed it will stall and then return to the
lobby and cycle the door.
After finishing the test remove power from the controller.
Replace SU-S12 and SUC-S11 connections on the controller.
Set the "Stall Time" to a value that will allow the elevator to make a complete run from the bottom floor
to the top floor.
Restore power to the controller.
Appendix A
8-1