GALaxy eHydro Elevator Controller
Table 7-6: Group Dispatch
Field Variable
Min
Asgn ParkF DO
0
AutoSVC tot T
10
AutoSVC T-out
0
Dis Opp HC T
10
Disabl Opp HC
0
DnPeak Contrl
0
Max
Initial
1
0
3200
120
1
0
30
10
15
0
1
0
Section 7 – Main CPU Adjustable Variables
Assign Parking Floor with Door Open. By default, we
only park cars that have the doors closed after a time
delay. This parameters allows to re-assign parking to
cars with doors open as long as they do not have a
direction to run.
Auto Service Time Out Time. This time, in seconds, is
used in conjunction with 'Auto SVC tm-out' and is the
amount of time that the group will wait before
setting a 'not moving/responding' car as timed out.
Auto Service Time-out.
0 = Disable,
1 = Enable
When this parameter is enabled and 'Auto SVC tot
TM' parameter time is set accordingly, each car is
checked for answering assigned hall calls. If the car
does not move to answer calls in the required time, it
is put into AST service. Hall calls that are assigned to
that car are reassigned to working cars in the group.
The group then periodically assigns hall calls to the
AST car to verify if it can be put back into the group
for normal operation.
Disable Opposite Hall Call Time. Specify amount of
time the opposite hall call will be disabled.
Disable Opposite Hall Call after initial hall call is
entered. When the first up or down hall call is
registered, disable opposite call for the time set; +1 =
Front HC riser, +2 = Rear HC riser, +4 = IR front HC
riser,+8 = IR rear HC riser
Down Peak Control
0 = Normal down peak
1 = Heavy down peak