GALaxy eHydro Elevator Controller
Table 6-0: Main CPU Faults
Faults
HC DrvBd Rx from
Bot
HC DrvBd Tx to Bot
HC DvrBd Rx from
Top
HC DvrBd Too Few
Dev
HC DvrBd TooMany
Dev
Description
The Hall Call Driver
Board is not receiving
packets from the
bottom station.
The Hall Call Driver
Board is cannot
internally read
information that it
transmitter to the
bottom station
The Hall Call Driver
Board is not receiving
packets from the top
station.
The Hall Call Driver
Board has too few
stations detected
based on the
controller
configuration. This
fault will only trigger if
loop is closed.
The Hall Call Driver
Board has too many
stations detected
based on the
controller
configuration.
Section 6 – Main CPU Faults & Detailed Faults
Possible Cause/Suggested Fix
• Cable is bad or disconnected
• Cables going to wrong port (i.e., switched TO ABOVE and
TO BELOW)
• Transmitter from device above or below is bad, check
faults for that device.
• Receiver on board is bad – replace device
• Cable connecting two devices could be flip- flopped (i.e.,
gray wire goes from pin 1 on one end to pin 8 on the other
end). Disconnect cable, and if fault changes to Rx Fault, the
problem is the cable.
• Cables going to wrong port (i.e., switched TO ABOVE and
TO BELOW)
• Transmitter is bad – replace the Device.
• Cable is bad or disconnected
• Cables going to wrong port (i.e., switched TO ABOVE and
TO BELOW)
• Transmitter from device above or below is bad, check
faults for that device.
• Receiver on board is bad – replace device
• Check configuration and number of stations
• Check configuration and number of stations