GALaxy eHydro Elevator Controller
Table 6-0: Main CPU Faults
Faults
FVARS Tbl
Chksum Err
Gate Switch Fault
Gate/Lock Byp Sw Flt
Governor Switch Flt
GOVRi Input On Fault
GRCan Bus Off Error
Description
Field Variables Table
Checksum Error. The
verification checksum
for the main field
variable table has
failed. During power
outages or brown-
outs, enough noise
can be generated on
the 5V DC supply to
cause an error in
reading the field
variables table on
power up. For this
reason, we keep the
data in two separate
tables. If only one
table checksum error
occurs, then valid data
will be restored.
The Gate Switch failed
on while the door was
open.
The gate or lock
bypass switch was on
while the car was NOT
on car top inspection.
Governor Switch
Tripped.
GOVRi input failed on.
GRCan Bus Off Error.
The Can bus has been
inactive for too long a
period of time.
Section 6 – Main CPU Faults & Detailed Faults
Possible Cause/Suggested Fix
• No action is required.
• Gate switch not adjusted properly.
• GS input failed on. Replace GS input on 1102 board.
• Gate or Lock bypass switch on the controller 1121 board is
in the on position.• Gate or Lock bypass input failed on.
Replace GBP OR LBP input chip on 1121 board.
• Verify that the governor switch is set properly.
• The GOVRi input chip failed. Replace the chip.
• The governor reset switch is stuck on.
• The GOVRi input is jumped on.
• Faulty CAN bus wiring. Check the Can bus terminal
connections on all boards.
6-60