GALaxy eHydro Elevator Controller
Table 7-6: Group Dispatch
Field Variable
Min
Priorty Floor
0
Priorty Flr T
6
Up Peak Pool
0
Up Peak Time
0
Up Pk Contrl
0
UpPk CC Count
1
UpPk Trig Cnt
1
Max
Initial
Top
0
Floor
254
60
Number
1
Cars
3200
180
1
0
40
3
100
3
Section 7 – Main CPU Adjustable Variables
High Priority Floor. When this parameter is set to a
floor number other than zero the high priority
operation is activated. If there is a call latched at the
high priority floor and the timer set from the 'High
Priority TM' expires, the group will choose the best
car by considering only car calls. It will remove all hall
calls on that best car except for the priority floor hall
call. The car will serve all car calls and then service
the priority floor before being assigned another hall
call from the group.
High Priority Time. Works in conjunction with
parameter 'High Priority Floor', it is the amount of
time to wait before removing hall calls assigned to
the selected best car.
Up Peak Pool. Number of cars to be utilized for up
peak.
Up Peak Duration Time. The duration time for up
peak operation once up peak is activated. If set to
zero, up peak operation will never turn on.
Up Peak Control. 0 = Normal up peak 1 = Heavy up
peak
Up Peak Car Call Count. Number of car calls the car
must have when leaving the lobby to count as an up
peak trigger.
Up Peak Trigger Count. The number of up peak
triggers that are set within the up peak trigger time to
activate up peak operation. Up peak triggers are
counted when the car leaves the lobby with the load
dispatch input set or with the more car calls than the
up peak car call count.
7-31