GALaxy eHydro Elevator Controller
Table 7-3: Car Options
Field Variable
Min
DO No
0
ActvDOL
DOB Over
0
Nudg
DoorOpenL Ctl
0
Double Stroke
0
EE Canc Dwell
0
Bottom
Handcap T Flr
Floor
HB/PI DisNoFl
0
Max
Initial
Units
1
0
-
1
0
-
16
0
-
1
1
-
1
0
-
Top
1
floor
Floor
1
0
-
Section 7 – Main CPU Adjustable Variables
Door Open Output When No Active DOL. When the
door is fully open and hits the DOL, the DO is turned
off and stays off even if the door drifts off of DOL.
With this bit set, the DO output will turn on any time
the DOL is lost.
DOB Over Nudging. If set, the door open button will
open the door when the door is nudging closed.
Door Open Light Control. The way 'DoorOpenL Ctrl'
parameter works is as below:
+1 = Set OPENL on phase 1 completed
+2 = Set OPENL on RTL return to lobby
+4 = Set OPENL on emp returned home with doors
open, also sets OPENL on emp and selected to run
+8 = Set OPENL on when Lobby Floor
+16 = Set OPENL all the time
Double Stroke Gong Selection. Select 1 or 2 gongs for
down hall calls.
0 = 1 gong
1 = 2 gongs.
Electric Eye Cancel Dwell. By turning this parameter
on you disable the short dwelling door time from the
electric eye signal (EE). By default the short dwelling
time is enabled.
Handicap Time Floor. If the job is configured to have
an extended door input at a hall station, this
parameter configures the floor number when
parameter will change door timing. It will operate for
EDHL only
Handicap Buzzer/PI Display Control. When set to 1,
do not sound HB or update floor PI when passing an
invalid floor.
7-10