GAL GALaxy eHydro Manual page 196

Elevator controller
Table of Contents

Advertisement

GALaxy eHydro Elevator Controller
Table 7-3: Car Options
Field Variable
Min
Invert CLF
0
Invert LOS
0
Invert LPS
0
Invert TPL
0
ISER Outp Ctl
0
Lant Pref Dly
0
LbyLan NCU/IR
0
Min Door T En
0
Max
Initial
Units
1
1
-
1
0
-
1
0
-
1
0
-
7
0
-
3
0
sec
1
0
-
1
0
-
Section 7 – Main CPU Adjustable Variables
Invert The Logic For The Car Light Fan. If set to 0 car
light fan is normally open. If set to 1 car light fan is
normally closed.
Invert Low Oil Switch (LOS)
Invert Low Pressure Switch (LPS)
Invert Temperature Low Switch (TPL)
Invert In Service Output.
1 = The in service light output is turned off when the
car is in service instead of turned on.
2 = The ISER output will function as an elevator in use
light.
4 = This output functions as out of service from a
shutdown and does not include independent,
inspection or recovery mode.
Lantern Preference Change Delay. When the
direction preference for the elevator changes, we
clear the lanterns and wait for this amount of time
before the lanterns are turned on again.
Lobby Lantern NCU/IR.
0 = Light the lanterns on IR service at each floor. The
lantern will not light at the lobby if next up operation
is selected because the IR car will not be selected to
be the next up car.
1 = The IR car will light the lantern at all the floors and
the lobby even with the system on next up operation.
Minimum Door Time Enable.
0 = Disabled
1 = The minimum door time for a car call or a hall call
is set from the car or hall call dwell timers and cannot
be shortened by the Door Close button.
7-11