GALaxy eHydro Elevator Controller
Set the Adjustable Variables – "NTS Proc Adj Vars" in the Controller.
2.7.2.2
The following parameters must be setup prior to learning any floor positions.
Set "Top Speed" to the contract speed of the job.
Set "Num Valid Fl" to the number of floors with openings on this elevator.
Set "UT Limit Dist" and "DT Limit Dist". If set to zero, the distance is set automatically from the
slowdown table in the manual. If the parameter is changed, it will not take effect until a learn
operation is done at the top and bottom floor. It is recommended to set both parameters to zero
unless the slowdown distance need to be adjusted.
Set "Can Baud Rate" to 0. 0 is 115.2K Baud. This parameter should not need to be changed.
2.7.2.3

Zero the Hoistway

After the NTS Processor parameters are setup, navigate to the Elevator Setup menu and select Learn
Hoistway. The diagram below, Figure 2-18, shows the initial part of Learn Hoistway process if done
from the machine room. To setup the hoistway from the car, you will only have to enter this menu the
first time to zero the hoistway table. Note that the number of valid floors and top speed will be verified
during this process. Be sure to select YES for First Time Setup and press ENTER. When you see the
message, "Setup Active. Hit Up or Dn to Scroll thru", press MODE to escape to the main menu. You
are now ready to setup the floors from the car.
Figure 2-18: Learn Hoistway From Car
Section 2 –Installation
2-15