GALaxy eHydro Elevator Controller
Table 7-3: Car Options
Field Variable
Min
OSERL OutCtl1
0
OSERL OutCtl2
0
Preopen Doors
0
RCF Output En
0
RCM Control
0
Max
Initial
Units
7
0
-
1
0
-
3
0
-
1
0
-
3
0
-
Section 7 – Main CPU Adjustable Variables
Out of Service Light Control.
+1 = Not responding to calls;
+2 = Between floors for over a minute
+4 = SS open.
When this parameter as well as OSERL OutCtrl 2 is set
to zero, the output will just operate as an Out of
service light.
Out of Service Light Control.
+ 1= Alarm.
When this parameter as well as OSERL OutCtrl 2 is set
to zero, the output will just operate as an Out of
service light.
Preopen Doors.
+1 = Will enable preopening of the doors. If retiring
cam used with auto door, RCM will also turn on at the
preopening point.
+2 = Exclude short floors.
Retiring Cam for Freight Output Enable. When you
turn on this parameter a retiring cam output will be
created in the controller, RCF, that mirrors the signal
from RCM. You need to reboot CPU every time you
change this parameter for change to take effect.
Retiring Cam Control.
1 = Hold the retiring cam up at the floor if there is no
pilot to open the door (manual doors). The retiring
cam will drop after 5 minutes.
2 = RCM output turns on when DZ hit to advance the
RCM ahead of the door open (auto door with retiring
cam) otherwise the default is that RCM turns on
when dead level. If preopening is set RCM and DO
turn on when DZ hit.