GALaxy eHydro Elevator Controller
Section 7 - Main CPU Adjustable Variables
This section includes all the CPU Adjustable Variables as well as the NTS Adjustable Variables, and the
Velocity Slowdown Table.
Table 7-1: Car Motion
Field Variable
Min
Acc DT Dist
0
Acc UT Dist
0
APS Dead
0.1
Zone
High Spd Ins
0
Preopen
0
Delay
Short Fl hsf
0
ShortFl Cntrl
0
Max
Initial
Units
120
24
inches
120
24
inches
0.5
0.25
inches
1
0
-
3200
0.5
sec
1
0
-
7
0
-
Section 7 – Main CPU Adjustable Variables
Description
Access DT Distance. Distance from DT limit for the
bottom access limit to be software activated.
The controller counts pulses from the DT limit.
Access UT Distance. Distance from UT limit for the top
access limit to be software activated.
The controller counts pulses from the UT limit.
APS Selector Dead Zone. This is the distance that the car
can move without calling for a relevel.
High Speed Inspection. Set to run car on high speed
while on inspection.
Preopen Delay. Delay time to preopen the door starting
from when the car reaches 3 inches from dead level and
the door can safely be opened.
Short Floor hsf (high speed flag) with no high speed
valve. Controller makes a run but only with one valve.
0=HS Output
1=No HS Out
Short Floor Control.
0 = Default is that the car relevels to the short floor.
+1 = Car will make a run between very short floors
instead of re- leveling.
+2 = Short floor slowdown magnets between short floors
(non-distance feedback).
+4 = Mid Short floor slowdown magnets between short
floors (non-distance feedback).