GAL GALaxy eHydro Manual page 191

Elevator controller
Table of Contents

Advertisement

GALaxy eHydro Elevator Controller
Table 7-2: Car Timers
Field Variable
Min
Lobby Dwell
1
Lt/Fan Time
30
ManDo Buz Dly
0
Mx Door Hld T
0
NonInterfer T
1
Nudging Time
20
OSER BtwFlr T
0
OSER NoCall T
0
Max
Initial
Units
60
5
sec
3200
360
sec
900
0
sec
3200
0
sec
60
2
sec
3200
60
sec
900
60
sec
900
600
sec
Section 7 – Main CPU Adjustable Variables
Description
Lobby Dwell. Door open dwell time for a car at the
lobby.
Generator Run/Cab Light/Fan Time. Length of time
to leave the generator running or the Cab light and
fan on after there is no longer a demand to run.
Manual Door Buzzer Delay. On a car with manual
doors, sound the buzzer if the door is left open and a
call is entered after this time delay. This function is
disabled when set to zero.
Maximum Door Hold Time. Maximum time to be
allowed when the extended dwelling input (ED) is
pressed. If set to zero, there will be no limit on how
long the car will be held on ED. When set to a value,
this will be the maximum allowed time for the car to
be held by ED input, then car will go on regular
dwelling timers (car or hall call dwelling timers)
Non-Interference Time. Time between when you stop
and when you can run again.
Nudging Time. Delay time for a door to be held
before going into nudging.
Out of Service Between Floors Time. Timer to
control the OSERL output. Used with OSERL Control
option 1 for 'between floors for over a minute' set to
2.
Out of Service Not Responding to Calls Time. Timer
to control the OSERL output. Used with OSERL Control
option 1 for 'not responding to calls' set to 1.
7-6