GALaxy eHydro Elevator Controller
Table 7-5: Emergency Services
Field Variable
Min
HSV DoorCl CC
0
HWS2 Fire Loc
0
HWS2 Fire Ret
0
MachRm FirRet
0
Med CCS Ovrrd
0
Bottom
Med Em Floor
Floor
Med Em Sw Loc
0
MedDoorReopen
0
MedInd Ovrrid
0
Max
Initial
Units
1
0
-
1
50
-
1
0
-
1
0
-
1
0
-
Top
1
floor
Floor
1
0
-
2
0
-
2
0
-
Section 7 – Main CPU Adjustable Variables
Hospital Service Close door Car Call. Close the
doors from a car call when the car is on Hospital
Service.
Fire Service Hoistway HWS2 Sensor Location .
0 = Same HW
1 = Separate hoistway
Second Hoistway Fire Service Sensor Return
Option.
0 = Main recall floor
1 = Alternate recall floor.
Machine Room Fire Sensor Return Floor Selection.
0 = Return to the Main fire floor,
1 = Return to the Alternate fire floor.
Medical Service Override Car Call Security.
1 = Medical service car will override car call security.
Medical Emergency Return floor.
Medical Emergency Switch Location. Selects the
switch location for the front or rear door.
0 = Front
1 = Rear
Medical service Door Reopen. When car is on
medical Service, this parameter determines the
door open sequence for re-open:
0 = Stop,
1 = Constant pressure,
2 = Momentary to DOL
Medical Service Overrides Independent Control:
0 = Immediate,
1 = After Delay,
2 = No override
7-25