GALaxy eHydro Elevator Controller
Table 6-1: Device Faults from the CTCAN, GRCAN and MRCAN Serial Ports
Fault
Description
Hoistway Floor
Count = 0 Fault on
HW Fl
the NTS processor.
Cnt=0 F
The hoistway floor
table is not setup
properly.
Hoistway Valid Floor
Fault on the NTS
processor. The
device hoistway
table has the
HW Valid
hoistway learn flag
Fl F
set, indicating that it
had been setup but
the but one or more
floor is not valid. The
hoistway floor table
is not setup
properly.
NTS Processor has a
communications
SPI Com
fault on the SPI bus
Fault
to the 1132 Main
CPU Board.
Possible Cause/Suggested Fix
• Check the valid floor table of the NTS processor on the LCD Interface in
the Hoistway Table Valid Floor and Clips menu. Run car to the floor with
the position of the invalid floor or floors and learn the floor position.
• Complete the setup process.
• Faulty NTS processor. Replace the 1121 Main I/O board. Contact Tech
Support.
• Check the valid floor table of the NTS processor on the LCD Interface in
the Hoistway Table Valid Floor and Clips menu. Run car to the floor with
the position of the invalid floor or floors and learn the floor position.
• Complete the setup process.
• Faulty NTS processor. Replace the 1121 Main I/O board. Contact Tech
Support.
• Check that the 1132 Main CPU board is installed properly on the 1121
Main I/O board.
• Faulty 1132 Main CPU board. Replace the board.
• Faulty 1121 Main I/O board. Replace the board.
Section 6 – Main CPU Faults & Detailed Faults
6-86