GALaxy eHydro Elevator Controller
Table 7-5: Emergency Services
Field Variable
Min
Bottom
ALT Fire Flr
Floor
AltRcl FS Off
0
Aux. Fire Sw
0
CB Buzz ctrl
0
CB over FS
0
CB Over Ind
0
CB SingleCall
0
ClDoor F1 Rcl
0
Bottom
Em Pwr Floor
Floor
Max
Initial
Units
Top
2
floor
Floor
3
0
-
1
0
-
1
0
-
1
0
-
1
0
1
0
-
1
0
-
Top
1
floor
Floor
Section 7 – Main CPU Adjustable Variables
Alternate Fire Floor.
Alternate Floor Recall Fire Service Off.
+1 = Have the elevator recall back to the alternate
floor when the lobby fire switch is turned to the off
position and car recalled to the main fire floor.
+2 = Allows the car to return to the alternate
landing even if sensor was reset
Auxiliary Fire Switch. When set, the controller
expects an auxiliary hall fire switch to be used.
Code blue Buzzer Control.
1 = Turn buzzer on while in code blue recall
Code Blue over Fire Service.
+1 Enable to have code blue prevent car from
recalling in FS
Code Blue Override Independent.
1 = Wait for timer to expire and then recall the car
Code Blue Single Car Call.
0 = Car on Code Blue operation allows multiple car
calls on Hospital Service.
1 = Allow only a single call once place on Hospital
Service.
Close Door After Fire phase 1 Recall.
1 = Elevator will close the doors after phase 1 recall
and reopen from a hall call (Denver Fire service
amendment)
Emergency Power Recall Floor.
7-22