8.2 Reset Low Oil, Hot Oil, or MC/SPD Fault

To reset a Low Oil, Hot Oil or MC/SPD fault, first verify that the cause of the fault has been corrected and
then follow the directions below:
Place the car on machine room inspection.
From the LCD Interface, select the Elevator Setup menu and press the enter button.
Use the up or down button to select the appropriate reset menu and press enter.
Follow the directions on the screen to press the appropriate buttons to reset the device

8.3 Performing a Stop Ring Test

Place a call to the top floor.
Put the car on machine room INSPECTION.
Turn off the power to the controller
Place the jumper CN18 on TEST MODE (position 2-3).
Turn on power to the controller.
Run the car UP on inspection from the machine room until the car stops on the "Top Terminal
Limit".
Turn off power to the controller.
Install a temporary connection between GOV-H22 and TLH-H21.
Turn on power to the controller.
Run the car UP on inspection to perform the stop ring test.
After the stop ring test is completed, run the car DOWN on inspection until the car is level at the
top floor.
Turn off power to the controller.
Remove the temporary connection between GOV-H22 and TLH-H21.
Place the jumper CN18 on AUTO MODE (position 1-2).

8.4 Testing NTSD

The NTS processor has a separate CAN channel to the SIL 3 APS selector head. The NTS processor
controls "UN", "UT", "DT", "DN".
In "HOISTWAY TABLES", "SET SLOWDOWN COUNTS", "SET SLOWDOWN COUNTS FOR ALL", set
"UP" to a count of 102 or 2 inches. This distance is closer than the UT distance. With the car at the
bottom floor set a call to the top floor. Notice the car slowdown normally but a "UT Limit Fault" is logged.
Reset the "UP" count back to its prior value. Place the car on Inspection mode this will render the normal
elevator stopping means inoperative. Run the car up on inspection verify the car stops 2 inches above the
top floor.
In "HOISTWAY TABLES", "SET SLOWDOWN COUNTS", "SET SLOWDOWN COUNTS FOR ALL", set
"DOWN" to a count of 102 or 2 inches. This distance is closer than the DT distance. With the car at the
top floor set a call to the bottom floor.
Notice the car slowdown normally but a "DT Limit Fault" is logged. Reset the "DOWN" count back to its
prior value. Place the car on Inspection mode this will render the normal elevator stopping means