GAL GALaxy eHydro Manual page 222

Elevator controller
Table of Contents

Advertisement

GALaxy eHydro Elevator Controller
Table 7-7: Group Options
Field Variable
Min
HCasg SecType
0
HCX-AssignETA
0
Invert HC Sec
0
IR Car
0
IR Control
0
Nmbr Vip Cars
0
OTS No
0
HCCanc
Max
Initial
Units
15
0
-
500
60
Sec
1
0
-
7
0
Car
7
0
Car
7
1
car
1
0
-
Section 7 – Main CPU Adjustable Variables
Description
Hall Call Assignment Security Type. Use with Special
Priority Service. Determines what hall calls should be
given a special priority. Settings are
1 = Up
2 = Down
4 = Up Rear
8 = Down Rear
Hall Call Cross Assignment ETA Limit. If ETA for hall
call assignment is greater than this ETA limit, the hall
call will be cross-assigned to the old group controller.
Invert Hall Call Security.
1 = Hall call security inputs are secured when the
security input goes off from a normally closed switch.
Normally, the security input must be on to secure the
hall call.
Inconspicuous Riser Car. This car is assigned all the IR
hall calls.
Inconspicuous Riser Control. This parameter alters
how IR riser service is activated or deactivated. 0 = IR
active from ICR or RICR input.
+1 = IR activated when any IR call is activated..
+2 = Finish car calls then answer IR calls,
+4 = Finish car call before going off IR.
Number of VIP Cars. Number of cars allow to service
VIP (priority service) calls at one time.
Out of Service No Hall Call Cancelled. Do not cancel
hall calls if cars are out of service. This is used in
accordance with cross assignment feature.
7-37