GALaxy eHydro Elevator Controller
Table 7-6: Group Dispatch
Field Variable
Min
Parking Flr 3
0
Parking Flr 4
0
Parking Flr 5
0
Parking Type
0
Parking Width
0
Max
Initial
Top
0
Floor
Top
0
Floor
Top
0
Floor
3
0
Top
0
Floor
Section 7 – Main CPU Adjustable Variables
Parking Floor 3. Floor to park the idle car. If set to
zero, the group will use number of hall call history to
decide where to park the car. The parking variable
must be set to at least 1 for this function to work. See
also Parking Type.
Parking Floor 4. Floor to park the idle car. If set to
zero, the group will use number of hall call history to
decide where to park the car. The parking variable
must be set to at least 1 for this function to work. See
also Parking Type.
Parking Floor 5. Floor to park the idle car. If set to
zero, the group will use number of hall call history to
decide where to park the car. The parking variable
must be set to at least 1 for this function to work. See
also Parking Type.
Parking Type. Determines the type of parking
operation that is implemented by the group. 0 = Park
free cars to floors with the most hall calls for that 15
minute period. 1 = Divide the hoistway by the
number of cars and place a car in each zone starting
with the lobby. 2 = Park cars according to the
adjustable variable parking floor. Note that during
parking, a car is always parked at the Lobby except
when the option for alternate parking floor is
selected through an input.
Parking Width. The number of floor that a car is
within to be considered parked at the parking floor.
See also Parking Type.
7-30