GALaxy eHydro Elevator Controller
Table 7-1: Car Motion
Field Variable
Min
Shrt Fl Dn SD
0
Shrt Fl Up SD
0
ShrtMidF
0
DnSD
ShrtMidF
0
UpSD
Soft Stop Tim
0.2
StopOn
0
PosCnt
Max
Initial
Units
30
0
sec
30
0
sec
30
0
sec
30
0
sec
5
1
sec
1
0
-
Section 7 – Main CPU Adjustable Variables
Description
Short Floor Down Slowdown. Hydro - There are no slow
down magnets between short floors. This is a timer to
run down high speed in seconds. If the timer is set to
zero, controller will immediately level looking for the
other zone. This parameter should only be used if second
selector is utilized.
Short Floor Up Slowdown. Hydro - There are no slow
down magnets between short floors. This is a timer to
run up high speed in seconds. If the timer is set to zero,
controller will immediately level looking for the other
zone. This parameter should only be used if second
selector is utilized.
Short Mid Floor Down Slowdown. Hydro - To be used in
second and higher short floor. There are no slow down
magnets between short floors. This is a timer to run
down high speed in seconds. If the timer is set to zero,
controller will immediately level looking for the other
zone. This parameter should only be used if second
selector is utilized.
Short Mid Floor Up Slowdown. Hydro - To be used in
second and higher short floor. There are no slow down
magnets between short floors.
This is a timer to run up high speed in seconds. If the
timer is set to zero, controller will immediately level
looking for the other zone. This parameter should only be
used if second selector is utilized.
Soft Stop Time. The time the motor is kept running after
the valve is turned off.
Stop On Position Count. Enable to stop the elevator on
position pulse count. Used only for tapeless application.
This requires cons file setting to be enabled and
readjustment of leveling sensors for it to work.