GALaxy eHydro Elevator Controller
Table 7-5: Emergency Services
Field Variable
Min
Fire Option 2
0
Fire Sw Loc
0
FireL Em Pwr
0
FireL OTS Ret
0
Flash CBLight
0
Hall Fire Lt
0
Hoistw FirRet
0
Max
Initial
Units
3
1
-
4
0
-
1
1
-
1
0
-
1
0
-
4
0
-
1
0
-
Section 7 – Main CPU Adjustable Variables
Fire Option 2.
+1 = Initiate a phase 2 recall only when the door is
open (Chicago fire).
+2 = Disable flashing FL on phase 2 (Chicago fire).
Fire Switch Location. Location of fire hall switch.
0 = Main/Alt Front,
1 = Main Rear/Alt Front,
2 = Main Front/Alt Rear,
3 = Main/Alt Rear,
4 = Set from Dispatcher Car selection.
Fire Light Control During Emergency Power. Enable
to cause the fire light FL to turn off if the car is not
selected to run.
Fire light Control for Out of Service Cars. Enabling
this parameter will turn off the fire light in the event
the car cannot recall for being out of service. It
could be in Earthquake, low oil, stall, etc.
Flash Code Blue Light. When set to 1 the code blue
light inside the car station will flash.
Hall Fire Light. The variable controls the FLH output
on the controller so it can be used for a hall fire light
or a fire security override. The default operation is
that FLH turns on while the car is on phase 1 or
phase 2 fire service.
+1 = On while phase 1 is in effect,
+2 = Flash FLH at 1 second intervals while activated,
+4 = FLH follows the Fire Light (FL) logic.
Hoistway Fire Sensor Return Floor Selection.
0 = Return to the Main fire floor,
1 = Return to the Alternate fire floor.
7-24