Complete The Installation Of Equipment - GAL GALaxy eHydro Manual

Elevator controller
Table of Contents

Advertisement

GALaxy eHydro Elevator Controller
Check/set parameters in the controller LCD user interface. See "eHydro Controller Settings" in
6)
Table 3-0.
Preset the following parameters from the LCD User Interface "Adjustable Variables" menu.
Adjustable Variables - Car Motion
APS Dead Zone = 0.25 inches
Stop On PosCnt = 0 (To be set in final setup)
High Spd Ins = 0 (0=slow speed inspection)
Table 3-0: eHydro Controller Settings
Preset the hydraulic valve according to the manufacturer's instructions.
7)
8)
Verify that the hydraulic pumping unit motor rotates in the correct direction.
9)
If the motor rotation is not correct, disconnect power and swap the motor starter wires connected
to the "Softstarter" terminals 1-L1 and 3-L2. After swapping these wires, re-apply power and
verify that the motor rotates in the correct direction.
If the Sprecher Schuh Softstarter generates a "Phase Reversal" fault, verify that dip switch 9 on
10)
the Softstarter is set properly. See the Sprecher Schuh Softstarter manual for instructions on the
proper setting for dip switch 9.
Verify that the elevator is safe to operate as a running platform and that all individuals are
clear of moving machinery.
Make sure all hoistway and car doors are closed.
11)
Adjust the speed of the platform in the up and down directions according to the hydraulic valve
manufacturer's instructions.

3.2.2 Complete the Installation of Equipment

Before beginning the adjustment process, the installation of all equipment should be complete including
the following items. See Section 2 for the installation procedures.
All field wiring, safety circuits, and safety devices should be installed.
The APS selector system should be installed including the "door zone bridge" guide clips.
All Terminal Limit switches should be installed.
All car doors and car door electric contacts or car door interlocks should be installed.
All hoist doors and hoistway door interlocks should be installed.
Section 3 – GALaxy Startup and Adjustment
Adjustable Variables - System Options
Hall Lan Baud = 3 (19,200)
Adjustable Variables - NTS Processor
Top Speed = Contract Speed
Number Valid Fl = Number of Valid Floors
UT Limit Dist = 0
DT Limit Dist = 0
3-4