GALaxy eHydro Elevator Controller
Table 6-0: Main CPU Faults
Faults
EP Recall Car 7 OTS
EP Recall Car 8 OTS
EPRecall Car1 Tim-ot
EPRecall Car2 Tim-ot
EPRecall Car3 Tim-ot
EPRecall Car4 Tim-ot
Description
Emergency Power
Recall Car Out of
Service Car 7. Car 7
was out of service
while elevators were
in
an Emergency Power
Recall Sequence.
Emergency Power
Recall Car Out of
Service Car 8. Car 8
was out of service
while elevators were
in an Emergency
Power Recall
Sequence.
Emergency Power
Recall Time-out Car 1.
Car 1 timeout while it
was in Emergency
power recall mode.
Emergency Power
Recall Time-out Car 2.
Car 2 timeout while it
was in Emergency
power recall mode.
Emergency Power
Recall Time-out Car 3.
Car 3 timeout while it
was in Emergency
power recall mode.
Emergency Power
Recall Time-out Car 4.
Car 4 timeout while it
was in Emergency
power recall mode.
Section 6 – Main CPU Faults & Detailed Faults
Possible Cause/Suggested Fix
• Check faults for car 7
• Check faults for car 8
• Make sure the field variable 'Recall Timeout' is set
properly to allow the car enough time to recover if it is
between floors and away from Emergency Power Floor•
Verify the speed of the car during recovery operation.
• Make sure the field variable 'Recall Timeout' is set
properly to allow the car enough time to recover if it is
between floors and away from Emergency Power Floor
• Verify the speed of the car during recovery operation.
• Make sure the field variable 'Recall Timeout' is set
properly to allow the car enough time to recover if it is
between floors and away from Emergency Power Floor
• Verify the speed of the car during recovery operation.
• Make sure the field variable 'Recall Timeout' is set
properly to allow the car enough time to recover if it is
between floors and away from Emergency Power Floor
• Verify the speed of the car during recovery operation.
6-55