GALaxy eHydro Elevator Controller
Table 7-7: Group Options
Field Variable
Min
GrpCC Sec OvT
1
Handicap Wait
0
HC Secur ctrl
0
HC X-AssignEn
0
Max
Initial
Units
240
60
Sec
255
0
Sec
2
0
-
5
0
-
Section 7 – Main CPU Adjustable Variables
Description
Group Car Call Security Override Timer. This is the
amount of time that the car call security is overridden
when a group car call security override button is
pressed.
Handicap Car Wait Time. Special operation that
when a passenger presses a handicap hall button, the
group adds this time to the ETA of all cars that do not
have enough capacity. See Handicap Capacity in car
options. Normally, if a car is at the floor of the
handicap hall call, it will get the assignment
regardless of the handicap capacity unless this value
is set to 255.
Hall Call Security Control. Set what riser the hall call
security inputs work with:
0 = Only standard hall calls
1 = Standard hall calls and Second Riser hall calls
2 = Only Second Riser hall calls
Hall Call Cross Assignment Enable.
1 = Front Hall Call Cross Assignment is enabled.
4 = Rear Hall Call Cross Assignment is enabled.
5 = Front and rear Hall Call Cross Assignment is
enabled. The group will look for cross assignment
calls as well as hall calls.
Power should be cycled on controller after this
variable is modified so all communications to all
devices are made.
2 = Hall Call Cross Cancellation is used and hall calls
are are not cancelled when all cars are out of service.
A setting of 3 for both hall call assignment and
cancellation is not valid and may cause unpredictable
results.
7-36