GALaxy eHydro Elevator Controller
Table 7-4: Service Options
Field Variable
Min
HEOF Override
0
IND DoorCl CC
0
Ind Over Sec
0
IND Rcl 2 Lby
0
Ins Door Clos
0
INSEC Out Ctl
0
Bottom
Lobby Floor
Floor
LW Anti-nuisn
0
Max
Initial
Units
3
0
-
1
0
-
7
0
-
1
0
-
1
0
-
1
0
-
Top
1
floor
Floor
50
0
count
Section 7 – Main CPU Adjustable Variables
Hall Elevator off Override.
1= Override Independent Service after timer expires
and then recall the car.
2 = Override Attendant Service after timer expires
and then recall the car.
Independent Door Close Car Call. Enable to close the
doors from a car call when the elevator is on
Independent.
Independent Overrides Security.
1 = Allow independent service to override security car
call lockouts.
2 = Override Security Floor Mask configurations.
4 = Override remote car call station.
Independent Recall to Lobby. Forces the car to recall
to the lobby when on independent and no calls are
made
Inspection Door Close.
1 = The door close output will turn on when the up or
down inspection run button is pressed.
INSEC - In Security Output Invert. Output located on
the car call security Board.
0 = Disabled
1 = Enabled
Lobby Floor.
Load Weighing Anti-Nuisance. Set to the maximum
number of car calls that can been entered before all
car calls are cancelled without the load switch LWA
input on. Once the load switch is on, all car calls will
stay latched. 0 = Disabled.
7-17