GALaxy eHydro Elevator Controller
Table 6-0: Main CPU Faults
Faults
EE Tst EE2
Failed ON
EE Tst EER1Faild OFF
EE Tst EER1
Faild ON
EE Tst EER2
Faild OFF
EE Tst EER2
Faild ON
Emrgncy Dispatch Flt
EP Recall Car 1 OTS
Description
Electric Eye Test.
Freight door electric
eye input EE2 failed
on.
Electric Eye Test.
Freight rear door
electric eye input
EER1 failed off.
Electric Eye Test.
Freight rear door
electric eye input
EER1 failed on.
Electric Eye Test.
Freight rear door
electric eye input
EER2 failed off.
Electric Eye Test.
Freight rear door
electric eye input
EER2 failed on.
Controllers went in
emergency Dispatch
Operation
Emergency Power
Recall Car Out of
Service Car 1. Car 1
was out of service
while elevators were
in
an Emergency Power
Recall Sequence.
Section 6 – Main CPU Faults & Detailed Faults
Possible Cause/Suggested Fix
• Verify that the electric eye input EE2 is off before the
electric eye test.
• Possible faulty electric eye device.
• Possible faulty EE2 input - replace the input.
• Verify that the electric eye input EER1 pulses on during the
electric eye test.• Possible faulty electric eye device.•
Possible faulty EER1 input - replace the input.
• Verify that the electric eye input EER1 is off before the
electric eye test.
• Possible faulty electric eye device.
• Possible faulty EER1 input - replace the input.
• Verify that the electric eye input EER2 pulses on during the
electric eye test.
• Possible faulty electric eye device.
• Possible faulty EER2 input - replace the input.
• Verify that the electric eye input EER2 is off before the
electric eye test.
• Possible faulty electric eye device.
• Possible faulty EER2 input - replace the input.
• Loss of communication with the hall call boards
• Loss of communication with the group
• Losing the HCP input
• Check faults for car 1
6-53