GALaxy eHydro Elevator Controller
Table 6-0: Main CPU Faults
Faults
Rear Door Close Flt
Rear Door Open
Fault
Rear Gate Sw Fault
Rear Mid Lock Fault
Rear Top Lock Fault
Description
The rear door did not
reach the Rear Door
Close Limit within the
door close protection
time.
The rear door did not
reach the Rear Door
Open Limit within the
door open protection
time.
The Rear Gate Switch
failed on while the
door was open.
The Middle Door Lock
failed on while the
door was open.
The Rear Top Door
Lock failed on while
the door was open.
Section 6 – Main CPU Faults & Detailed Faults
Possible Cause/Suggested Fix
• Rear Door Close Limit (DCLR) not adjusted properly.
• Faulty Rear Door Close Limit (DCLR). Replace DCRL input.
• Trash in door track preventing door from closing.
• Rear Door Open Limit (DOLR) not adjusted properly.•
Faulty Rear Door Open Limit (DOLR). Replace DOLR input.
• Rear Gate switch not adjusted properly.
• RGS input failed on. Replace RGS input.
• Faulty door lock.
• Jumper placed on door lock circuit.
• Rear door lock not adjusted properly.
• Faulty wiring to RLM input.
Faulty RLM and RLM-1 inputs (For this to occur both RLM
and RLM-1 inputs must fail on).
• DOLR input failed. Replace DOLR input chip.
• Rear door operator open limit is not adjusted properly
• Faulty door lock.
• Jumper placed on door lock circuit.
• Rear door lock not adjusted properly.
• Faulty wiring to DLT input.
Faulty DLT and DLT-1 inputs (For this to occur both DLT and
DLT-1 inputs must fail on).
• DOLR input failed. Replace DOLR input chip.
• Rear door operator open limit is not adjusted properly
6-74