GAL GALaxy eHydro Manual page 200

Elevator controller
Table of Contents

Advertisement

GALaxy eHydro Elevator Controller
Table 7-4: Service Options
Field Variable
Min
CEOF Control
0
DOB Over Sec
0
Door Hold Msg
0
ElevOff RetFl
0
Max
Initial
Units
7
0
-
5
0
-
1
0
-
Top
0
floor
Floor
Section 7 – Main CPU Adjustable Variables
Car Elevator Off Options.
+1 = Recall
+2 = Keep Door Open
+4 = Turn off CLF
DOB Override Security. This parameter allows the car
to open the door at a secured floor when the car is
secured from the following conditions:
1 = The DOB will be allowed to open the door at any
secured floor.
2 = The DOB can open the door at floors secured from
group security floor mask table.
3 = Allows the DOB to open the front door at floors
secured by car call lockout security (switches or card
reader).
4 = Allows the DOB to open the rear door at floors
secured from rear car call lockout security.
5 = Allows the DOB to open the door at floors locked
out by group security floor mask tables when the car
is also on independent.
Door Hold Message. Set to enable Extended Door
Time Message Indicator in CE Driver board
Elevator Off Return Floor. Related to HEOF input.
This setting is to be used in conjunction with 'Elev Off
Ctl = +1'. If the elevator is configured to recall, this
parameter will determine what floor the car should
be recalled to in elevator off mode. if Parameter is set
to zero, car will be returned to the Lobby.
7-15