the "Reset Low Oil" push the enter button, then place the controller inspection switch into the auto
position. Turn the fire service Phase I switch to the RESET position then back to the OFF position.
While the car is at the top floor, turn the fire service Phase I hall switch to the ON position. While the car is
returning, CAREFULLY install a temporary connection from FEP terminal to EMP terminal. If the elevator
is above the recall floor the elevator will stop at the recall floor and open its doors. If the elevator is below
the recall floor the elevator will stop at the bottom floor and open its doors. The doors will close after the
door time. Press the door open button and verify that the doors will open. To restore the car to normal
operation, remove the temporary connection from FET to EMP. Turn the fire service Phase I switch to the
RESET position then back to the OFF position.
Turn the fire service Phase I hall switch to the ON position. After the elevator has returned to the recall
floor and opened the doors, CAREFULLY install a temporary connection from S10 terminal to LOS
terminal. If a normally closed switch is being used, then CAREFULLY remove the wire from the LOS
terminal. Verify that the doors close and the fire light flashes on and off. To restore the car to normal
operation, remove the temporary connection from S10 to LOS. If a normally closed switch is used,
replace the wire back on LOS. Move the controller inspection switch to the inspection position, on the
LCD Board GALX-1005N push the up button to go to "RESET FAULTS", push the enter button, push the
up button to go to the "Reset Low Oil" push the enter button, then place the controller inspection switch
into the auto position. Turn the fire service Phase I switch to the RESET position then back to the OFF
position.
Turn the fire service Phase I hall switch to the ON position. After the elevator has returned to the recall
floor and opened the doors, CAREFULLY install a temporary connection from FEP terminal to EMP
terminal. Verify that the doors close and the fire light flashes on and off. To restore the car to normal
operation, remove the temporary connection from FEP to EMP. Turn the fire service Phase I switch to the
RESET position then back to the OFF position.

8.12 Testing Phase 2 Operation Under Special Conditions

Turn the fire service Phase I hall switch to the ON position. After the elevator has returned to the recall
floor and opened the doors turn the In Car Fire Service Phase II switch to the ON position. CAREFULLY
install a temporary connection from LC terminal to LOS terminal. If a normally closed switch is used, then
CAREFULLY remove the wire from the LOS terminal. Verify the fire light flashes on and off. Verify that
only calls below the elevator will register. To restore the car to normal operation, remove the temporary
connection from LC to LOS. If a normally closed switch is used, replace the wire back on LOS. Move the
controller inspection switch to the inspection position, on the LCD Board GALX-1005 push the up button
to go to "RESET FAULTS", push the enter button, push the up button to go to the "Reset Low Oil" push
the enter button, then place the controller inspection switch into the auto position. Turn the fire service
Phase II switch to the OFF position. Turn the fire service Phase I switch to the RESET position then back
to the OFF position.
Turn the fire service Phase I hall switch to the ON position. After the elevator has returned to the recall
floor and opened the doors turn the in car fire service phase II switch to the ON position. CAREFULLY
install a temporary connection from FEP terminal to EMP terminal. Verify the fire light flashes on and off.
Verify that only calls below the elevator will register. To restore the car to normal operation, remove the
temporary connection from FEP to EMP. Turn the fire service Phase II switch to the OFF position. Turn
the fire service Phase I switch to the RESET position then back to the OFF position.
8-5