Contents Of The Fieldbus Status Word - ABB ACS880 Firmware Manual

Dc/dc converter control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

196 Fieldbus control through a fieldbus adapter

Contents of the fieldbus Status word

Bit
Name
0
Ready to switch
ON
1
Ready run
2
Ready ref
3
Tripped
4
-
5
-
6
-
7
Warning
8
Operating
9
Remote
10
Ready for load
11
User bit 0
12
User bit 1
13
User bit 2
14
Charging
15
User bit 3
Value
Description
1
Ready to switch ON
Note: If the DC/DC converter unit is switched off, the Start enable
must be on for Ready to switch ON = 1. If the DC/DC converter unit is
switched on, Ready to switch ON = 1 regardless of the Start enable.
0
Not ready to switch ON
1
Ready to operate. Start command is on.
0
Start command is not given.
1
Operation enabled
0
Operation inhibited
1
Fault
0
No fault active
1
Not in use.
0
Not in use.
1
Not in use.
0
Not in use.
1
Not in use.
0
Not in use.
1
A warning is active
0
No warnings active
1
DC/DC converter is running.
0
DC/DC converter is not running.
1
Control location: REMOTE (EXT1 or EXT2).
0
Control location: LOCAL.
1
Ready for load.
0
Not ready for load.
1
See parameter
0
See parameter
1
See parameter
0
See parameter
1
See parameter
0
See parameter
1
Charging state is active.
0
Charging state is not active.
1
See parameter
0
See parameter
106.30 MSW bit 11
sel.
106.30 MSW bit 11
sel.
106.31 MSW bit 12
sel.
106.31 MSW bit 12
sel.
106.32 MSW bit 13
sel.
106.32 MSW bit 13
sel.
106.33 MSW bit 15
sel.
106.33 MSW bit 15
sel.

Hide quick links:

Advertisement

Table of Contents
loading