External Torque Limitation - Lenze i950 Commissioning Manual

Servo inverters
Hide thumbs Also See for i950:
Table of Contents

Advertisement

7.4

External torque limitation

The external torque limit is defined via the External torque limit parameter.
The external torque limit is activated with bit 22 of the Control signal parameter.
40x5040:010
Bit 22 of the Status signals parameter indicates whether the external torque limit is active.
Bit 22
As long as the external torque limit remains inactive, the two parameters Positive torque limit
and Negative torque limit define what torque limits apply.
Positive torque limit
40x500A:128
Negative torque limit
40x500A:129
The function mode of the external torque limit is set via the Impact of external speed limit
parameter.
The following settings are possible via this parameter:
Fig. 48: 0x5040:003 = 0: Setting affects the positive and negative torque limit
Fig. 49: 0x5040:003 = 1: Setting affects the positive torque limit
Fig. 50: 0x5040:003 = 2: Setting affects the negative torque limit
Configuring the "Electronic Gearbox" TA
5040:010 (Bit 31)
5040:017
0x500A:128
5040:017
0x500A:129
5040:010 (Bit 31)
5040:017
0x500A:128
0x500A:129
5040:010 (Bit 31)
5040:017
0x500A:129
0x500A:128
External torque limitation
40x5040:017
0x60E0
0x60E1
0x60E0
0x60E1
0x60E1
0x60E0
115