16.3.1.4

Device description file

The device description file must be installed in the engineering tool for configuring the net-
work (e. g. Siemens »TIA Portal«).
Download of GSDML files
The name of the device description file is as follows:
"GSDML-V<x>.<zz>-Lenze-I<NNN>PN<Version>-<yyyy><mm><dd>.xml".
Wildcard
Info
x
Major version of the used GSDML scheme
zz
One-digit or two-digit minor version of the used GSDML scheme
NNN
Specifying the inverter name, e. g. i<550>, i<950>, ...
Version
First software version that can be used with this GSDML.
yyyy
Year of publication
mm
Month of publication
dd
Day of publication
Define the user data length
The configuration of 1 ... 16 process data double words (4 ... 64 bytes) and 8 safety data words
is supported.
Examples of selecting the device description file:
"IEC 8 DWords I/O": 8 process data double words only in slot 1 of the PROFINET telegram)
"Safety module 4 DWords": 4 safety double words (only in slot 2 of the PROFINET telegram
when the extended safety engineering is used simultaneously)
16.3.1.5
Establishing a connection to the »EASY Starter« via PROFINET
To establish a communication link to the inverter via PROFINET ports X2x6/X2x7, proceed as
follows:
Requirements:
The network interface of the engineering PC provided for the connection is parameterised
for the PROFINET IP subnetwork.
A valid IP configuration is set in the inverter.
Tools required:
Engineering PC with installed »EASY Starter«.
Standard Ethernet cable from CAT 5/5e
1. Plug the network cable into one of the two PROFINET ports X2x6 / X2x7 of the inverter.
2. Use the network cable to connect the inverter to the PC on which »EASY Starter« is instal-
led.
3. Start the »EASY Starter«.
The "Add devices" dialog is shown.
4. Select the "PROFINET " connection.
5. Enter the PROFINET IP address of the inverter.
6. Press the Insert button.
Once a connection has been successfully established, the inverter is displayed in the device
list. The tabs in »EASY Starter« then provide access to the inverter parameters.
4Station name and IP configuration
Configuring the network
Commissioning
^ 334
PROFINET