Configuring the network
PROFINET

Basic setting and options

16.3.2
Basic setting and options
16.3.2.1

Station name and IP configuration

The station name and the IP configuration can be assigned via the IO-Controller. These set-
tings enable the IO-Controller to identify the inverter in the network and manage the data
exchange.
The station name and the IP configuration can also be assigned via the »EASY Starter«:
The station name of the inverter must be entered with permissible characters according to
the PROFINET specification.
Display of the currently used station name:
The IP configuration comprises the assignments of:
IP address
0x2381:001
Subnet mask
0x2381:002
Gateway address
0x2381:003
Display of the currently used IP configuration:
Save the station name and the IP configuration in the inverter with mains failure
protection in order that the inverter can be identified via Ethernet if the IO Con-
troller is switched off.
See:
4Saving the parameter settings
An invalid station name or the assignment of invalid combinations of IP address,
subnet mask and gateway address may prevent a connection to PROFINET.
In case of impermissible settings, the red LED "BUS ERR" is blinking and the
error message "PROFINET: stack initialisation error [0x8192]" is displayed.
4LED status display
Parameter
Address
Name / setting range / [default setting]
0x2381:001
PROFINET settings: IP address
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
0x2381:002
PROFINET settings: Subnet
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
0x2381:003
PROFINET settings: Gateway
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
0x2381:004
PROFINET settings: Station name
0x2381:005
PROFINET settings: I&M1 System designation
0x2381:006
PROFINET settings: I&M1 Installation site
0x2381:007
PROFINET settings: I&M2 Installation date
0x2381:008
PROFINET settings: I&M3 additional information
0x2381:009
PROFINET settings: I&M4 signature code
["000000000000000000000000000000000000000000
0000000000000000000000000000000000000000000
00000000000000000000000"]
334
40x2381:004
40x2382:004
40x2382:001
0x2022:003
^ 36
^ 339
...
0x2382:003
Info
Set IP address
• A changed value will only be effective after the PROFINET communica-
tion is restarted
(0x2380
= 1).
Set subnet mask
• A changed value will only be effective after the PROFINET communica-
tion is restarted
(0x2380
= 1).
Set gateway address
• A changed value will only be effective after the PROFINET communica-
tion is restarted
(0x2380
= 1).
• The gateway address is valid if the network address of the IP address
is identical to the gateway address. In this case, no gateway function-
ality is used.
• DHCP is not supported.
Set station name
• A changed value will only be effective after the PROFINET communica-
tion is restarted
(0x2380
= 1).
Input/output of the I&M1 system designation
• The default setting is an empty string.
Input/output of the I&M1 location identification code
• The default setting is an empty string.
Input/output of the I&M2 date of installation
• The default setting is an empty string.
Input/output of the I&M3 additional information
• The default setting is an empty string.
Input/output of the I&M4 signature
• The default setting is an empty string.