Configuring the network
EtherCAT

Parameter data transfer

16.2.4
Parameter data transfer
For configuring and diagnosing the EtherCAT devices, the parameters are accessed by
means of acyclic communication.
Parameter data is transferred as SDOs (Service Data Objects).
The SDO services enable the writing and reading access to parameters, EtherCAT objects
and CiA 402 objects.
Process input data (CiA 402 objects)
Process output data (CiA 402 objects)
The transfer of parameter data is usually not time-critical.
Parameter data is, for instance, operating parameters, motor data and diagnostic informa-
tion.
The content of this section is currently being processed.
SDO return values
If an SDO request is evaluated negatively, a corresponding error code is output:
Index
Description
0x00000000
No fault.
0x05030000
The state of the toggle bit has not changed.
0x05040000
SDO protocol time-out.
0x05040001
Invalid or unknown specification symbol for the client/server command.
0x05040005
The space in the main memory is not sufficient.
0x06010000
Unsupported access to an object.
0x06010001
Read access to a write-only object.
0x06010002
Write access to a read-only object.
0x06020000
An object is not available in the object directory.
0x06040041
An object cannot be mapped into the PDO.
0x06040042
The number and/or length of the mapped objects would exceed the PDO length.
0x06040043
General parameter incompatibility.
0x06040047
General internal incompatibility in the device.
0x06060000
The access has failed due to errors in the hardware.
0x06070010
The data type or the parameter length do not match.
0x06070012
Wrong data type: The parameter length is too big.
0x06070013
Wrong data type: The parameter length is too small.
0x06090011
A subindex is not available.
0x06090030
The value range for parameters is too big (only in case of write access).
0x06090031
The parameter value is too high.
0x06090032
The parameter value is too low.
0x06090036
The maximum value is smaller than the minimum value.
0x08000000
General fault.
0x08000020
Data cannot be transferred to the application or saved in the application.
0x08000021
Due to local control, the data cannot be transferred to the application or saved in the application.
0x08000022
Due to the current device state, the data cannot be transferred to the application or saved in the application.
0x08000023
The dynamic object directory generation has failed or no object directory is available.
16.2.5

Monitoring

The content of this section is currently being processed.
The parameters for setting network monitoring functions are described below.
Parameter
Address
Name / setting range / [default setting]
0x10F1:001
Error settings: Local error reaction
2 Device specific state
0x10F1:002
Error settings: Sync error counter limit
0 ... [20] ... 32
318
^ 159
^ 161
Info
An error response takes place exclusively via the inverter.
Setting for PDO frame failure detection.
When the internal telegram failure error counter reaches the value set
here, the inverter changes to the "Safe-Operational" state and causes an
error (CiA402 error code 0x8700).