13.11.2

Manual "tension/frequency" test mode

Functional description
In case of devices that correspond to the "dual use regulation" (EC 428/2009),
values higher than + 599 Hz up to lower than - 599 Hz do not increase the out-
put frequency. Please observe the deadband occurring in this case.
Further information can be found in the section
tions".
^ 276
After the controller is enabled in this test mode, a rotary field voltage is output at the motor
terminals with the set output frequency f
If the selected frequency is positive, the motor should rotate clockwise when looking at
the A side of the motor. If this is not the case, the motor phases are connected incorrectly.
The output voltage level is determined by the following equation
Equation for calculating the output voltage
Parameter
0x2835:002
0x2B01:001
0x2B01:002
The manual "voltage / frequency" test mode also serves to check the wiring of the feedback
system.
If the feedback system of a synchronous motor is set correctly, an actual speed should be
displayed that can be calculated with the following equation (if the feedback system of an
asynchronous motor is set correctly, the actual speed is a bit lower due to the slip):
Equation for calculating the actual speed
Parameter
0x606C
0x2835:002
0x2C01:001
Conditions for the execution
The motor must rotate freely.
The servo inverter is error-free and in the "switched-on" device state.
Response of the motor during performance
The motor moves as a function of the set output frequency.
How to activate the manual "voltage/frequency" test mode:
1. Disable the inverter
4Enable
2. Change to the "voltage/frequency" test mode.
3. Enable the inverter to start the test mode.
4. To stop the test mode again:
Disable inverter.
Change back to the "CiA402 operating mode".
.
out
=
U
out
Symbol
V
out
f
out
V
rated
f
rated
=
n
act
zp
Symbol
n
act
f
out
zp
Motor
operation.
^ 296
40x2825
40x2825
Configuring the motor control
Manual "tension/frequency" test mode
"Frequency and speed limita-
U
rated
×
f
out
f
rated
Description
Current output voltage
Output frequency for test mode
Please observe the notes in the
section
"Frequency and speed limi-
tations".
^ 276
Base voltage
Base frequency
f
out
×
60
motor
Description
Velocity actual value
Output frequency for test mode
Number of motor pole pairs
= 1
= 0
Testing the motor control
Dimension unit
V
Hz
V
Hz
Dimension unit
rpm
Hz
279