Configuring the network
EtherCAT
Commissioning
Parameter
Address
Name / setting range / [default setting]
0x5850:001
Kommandos für Systembus EtherCAT-Master: Kommu-
nikation neu starten
0 No action/no error
1 Neustart
10 Busy
11 Cancelled
12 Faulted
16.2.2

Basic setting and options

The content of this section is currently being processed.
16.2.2.1

Synchronisation with "distributed clocks" (DC)

The content of this section is currently being processed.
Parameter
Address
Name / setting range / [default setting]
0x10F8
Actual time stamp
• Read only: x ns
0x2580:001
Distributed Clocks : Real time status
• Read only
0 Not adjusted
1 Adjusted once
2 Adjusted cyclically
0x2580:002
Distributed Clocks : First setting time
• Read only: x ns
0x2580:003
Distributed Clocks : Newest setting time
• Read only: x ns
0x2580:004
Distributed Clocks : Current time
• Read only: x ns
16.2.2.2

Parameterising additional functions

Parameter
Address
Name / setting range / [default setting]
0x2946:001
Speed limitation: Upper speed limit
-479999.999776482 ... [0] ... 479999.999776482 rpm
0x2946:002
Speed limitation: Lower speed limit
-479999.999776482 ... [0] ... 479999.999776482 rpm
0x2DD5
Torque setpoint
• Read only: x.xx Nm
314
Info
Info
The time information currently used by the inverter (the device time, so
to speak).
Since its switch-on, the inverter has not yet received any real time infor-
mation from outside.
The inverter still works with a time based on the time of the last switch-
off or the time stamp of the firmware.
Since its switch-on, the inverter has not yet received any real time infor-
mation from outside.
Display of the time when the inverter has received a real time informa-
tion from outside for the for first time after its switch-on.
In the "No real time information received yet", the value "0" is displayed.
Display of the time when the inverter has most recently received a real
time information from outside.
Display of the time information currently used by the inverter (device
time).
Info
Upper limit for the speed limitation.
• Setting is only effective with the selection "Upper speed limit [5]" in .
• Entry via keypad and Lenze Tools is in rpm!
• Via RPDO, the unit is vel. unit. and the scaling must be taken into
account.
• ± 480000 rpm = ±2 ^ 31 [n-unit]
Lower limit for speed limitation.
• Setting is only effective with the selection "Lower speed limit [5]" in .
• Entry via keypad and Lenze Tools is in rpm!
• Via RPDO, the unit is vel. unit. and the scaling must be taken into
account.
• ± 480000 rpm = ±2 ^ 31 [n-unit]
Display of the current torque setpoint.