Advanced commissioning
6.3 Adapt the default setting of the terminal strip
6.3.2

Digital outputs

Changing the function of a digital output
Table 6-4
0
r0052.00
r0052.01
r0052.02
r0052.03
r0052.04
r0052.05
r0052.06
r0052.07
The complete list of binector outputs is provided in the List Manual.
Application example: Changing the function of a digital output
168
Frequently used binector outputs (BO) of the inverter
Deactivating digital output
1 signal: Ready for switching on
1 signal: Ready
1 signal: Operation enabled
1 signal: Fault active
The inverter inverts signal
r0052.03 if it is interconnected to
a digital output.
0 signal: OFF2 active
0 signal: OFF3 active
1 signal: Switching on inhibited ac‐
tive
1 signal: Alarm active
Overview of the manuals (Page 519)
To change the function of a digital output, you must
interconnect the digital output with a binector output
of your choice.
Interconnecting signals in the inverter
(Page 503)
Binector outputs are marked with "BO" in the param‐
eter list of the List Manual.
r0052.08
r0052.09
r0052.10
r0052.11
r0052.13
r0052.14
r0052.15
r0053.00
r0053.02
r0053.06
To output inverter fault messages via digital output DO 1, you
must interconnect DO1 with these fault messages.
Set p0731 = 52.3
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
0 signal: Deviation, setpoint/actual
speed
1 signal: Control requested
1 signal: Maximum speed (p1082)
reached
0 signal: I, M, P limit reached
0 signal: Alarm overtemperature motor
1 signal: Motor CW rotation
0 signal: Alarm inverter overload
1 signal: DC braking active
1 signal: Speed > minimum speed
(p1080)
1 signal: Speed ≥ setpoint speed (r1119)
Converter with the CU250S-2 Control Units