5.4.4

Standard Drive Control

Procedure for application class [1]: Standard Drive Control
The wizard only displays the "setpoint input" if you configured an inverter with PROFINET or
PROFIBUS interface.
Select whether the inverter is connected to a higher-level control via the fieldbus.
Select whether the ramp-function generator for the speed setpoint is implemented in the higher-
level control or in the inverter.
Select the required function modules for your application.
Select the I/O configuration to preassign the inverter interfaces.
Set the applicable motor standard and the inverter supply voltage.
If an optional component is installed between inverter and motor, the corresponding setting
must be performed.
If a braking resistor is installed, you set the maximum braking power to which the braking
resistor will be subjected.
Select your motor.
If you use Startdrive, then this commissioning step is included in Step 5.
Enter the motor data according to the rating plate of your motor.
If you have selected a motor based on its article number, the data has already been entered.
Define whether the inverter actuates a motor holding brake.
Set the most important parameters to suit your application.
Select the technological application:
● [0] Constant load: Typical applications include conveyor drives
● [1] Speed-dependent load: Typical applications include pumps and fans
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Inverter function modules (Page 132)
Factory interface settings (Page 96)
Default setting of the interfaces (Page 98)
Commissioning
5.4 Quick commissioning with a PC
139