List Of Alarms And Faults - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage inverters built-in units with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

8.6

List of alarms and faults

Axxxxx Alarm
Fyyyyy: Fault
Table 8-8
The most important alarms and faults
Number
Cause
F01000
Software error in the CU
F01001
Floating point exception
F01015
Software error in the CU
F01018
Power-up aborted more than once
A01028
Configuration error
F01033
Switching over units: Reference pa‐
rameter value invalid
F01034
Switching over units: Calculation of
the parameter values after refer‐
ence value change unsuccessful
F01040
Parameters must be saved
F01044
Error loading data from memory
card
A01053
System overload measured
F01054
System limit exceeded
A01101
Memory card not available
F01105
CU: Insufficient memory
F01122
Frequency at the probe input too
high
F01205
CU: Time slice overflow
F01250
CU hardware fault
F01303
The DRIVE-CLiQ does not support
the requested function
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Remedy
Replace CU.
Switch off CU and switch on again.
Upgrade firmware or contact technical support.
1. Switch the module off and on again.
2. After this fault has been output, the module is powered up with the
factory settings.
3. Recommission the inverter.
Explanation: Parameterization on the memory card has been created with
a different type of module (Article number, MLFB).
Check the module parameters and recommission if necessary.
Set the value of the reference parameter not equal to 0.0 (p0304, p0305,
p0310, p0596, p2000, p2001, p2002, p2003, r2004).
Select the value of the reference parameter so that the parameters involved
can be calculated in the per unit notation (p0304, p0305, p0310, p0596,
p2000, p2001, p2002, p2003, r2004).
Save parameters (p0971).
Switch CU off and on again.
Replace memory card or CU.
The maximum computing power of the Control Unit was exceeded. The
following measures reduce the load on the Control Unit:
● Use only one data record (CDS and DDS)
● Only use the safety features of the basic functions
● Deactivate the technology controller
● Use the simple ramp-function generator rather than the extended ramp-
function generator
● Do not use any free function components
● Reduce the sampling time of the free function blocks
Insert a memory card or deactivate alarm A01101.
Activate message for a memory card that is not inserted
(Page 372)
Reduce number of data sets.
Reduce the frequency of the pulses at the probe input.
Contact technical support.
Replace CU.
A function requested by the Control Unit is not supported by a DRIVE-CLiQ
component.
Alarms, faults and system messages
8.6 List of alarms and faults
401