Current Derating Depending On The Pulse Frequency, 690 V Inverters - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage inverters built-in units with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Technical data
10.3 Technical data, PM240-2 Power Modules
10.3.11

Current derating depending on the pulse frequency, 690 V inverters

Article number
6SL3210-1PH21-4 . L0
6SL3210-1PH22-0 . L0
6SL3210-1PH22-3 . L0
6SL3210-1PH22-7 . L0
6SL3210-1PH23-5 . L0
6SL321 . -1PH24-2 . L0
6SL3210-1PH25-2 . L0
6SL321 . -1PH26-2 . L0
6SL3210-1PH28-0 . L0
6SL3210-1PH31-0 . L0
6SL3210-1PH31-2 . L0
6SL3210-1PH31-4 . L0
6SL3210-1PH31-7CL0
6SL3210-1PH32-1CL0
6SL3210-1PH32-5CL0
*) Factory setting
The permissible motor cable length depends on the particular cable type and the pulse frequency that
has been selected
470
LO power [kW]
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Pulse frequency [kHz]
2 *)
LO base load output current [A]
14
19
11.4
23
13.8
27
16.2
35
42
25.2
52
31.2
62
37.2
80
100
115
142
85.2
171
102.6
208
124.8
250
Converter with the CU250S-2 Control Units
4
8.4
21
48
60
69
150

Advertisement

Table of Contents
loading

Table of Contents